LOOK! Here are the common faults and solutions of gas boiler burner
时间:2021-12-20 浏览次数: 1160 作者: 加科

1. Turn on the power supply, press start, and the motor does not rotate

Cause of failure:

(1) Insufficient air pressure locking

(2) The solenoid valve is not tight and the connector leaks. Check the locking

(3) Thermal relay open circuit

(4) At least one of the conditional circuits is not tenable (water level, pressure, temperature and whether the program controller is powered on and started)

Solution:

(1) Adjust the air pressure to the specified value

(2) Clean or repair the solenoid valve pipe joint

(3) Press reset to check the components for damage and motor current

(4) Check whether the water level, pressure and temperature exceed the limit

2. Turn off the burner immediately after it is lit

Cause of failure:

(1) The air pressure is insufficient, the pressure drop is too large, and the air supply flow is too small

(2) The air volume is too small, the combustion is insufficient, and the smoke color is thick

(3) The air volume is too large and white air appears

Solution:

(1) Readjust the air pressure and clean the filter screen

(2) Readjust

(3) Readjust

3. White smoke from burner

Cause of failure:

(1) The air volume is too small

(2) The air humidity is too high

(3) Low exhaust temperature

Solution:

(1) Turn down the damper

(2) Appropriately reduce the air volume and increase the inlet air temperature

(3) Take measures to improve the exhaust temperature


咨询热线
  • 座机:0531-83659330
  • 传真:0531-83382689
  • 邮箱:admin@gaco.cc
  • 总部地址:山东济南市章丘区宁石路9号
最新动态
加科助力君乐宝低氮改造获新助力
加科助力君乐宝低氮改造获新助力

近日,加科燃烧器圆满完成江苏君乐宝乳业有限公司2台低氮燃烧器项目的安装与调试工作,为乳业生产的高效、环保运行注入···

+MORE
292025-07
加科携手云天化,共启低氮新征程
加科携手云天化,共启低氮新征程

近日,加科燃烧器顺利完成对青海云天化国际化肥有限公司2台25吨低氮燃烧器的改造项目,标志着双方在环保与能源效率提升···

+MORE
232025-07
联系我们

24小时竭诚为您服务

15563365608(微信同号)

地址:山东省济南市章丘区宁石路9号

邮箱:admin@gaco.cc

电话
0531-83659330
微信
微信二位码
留言
返回顶部
加科(山东)智能装备有限公司 备案号:鲁ICP备17025986号-5
首页
产品
咨询
应用
服务